- MODEL: Nx103(1:1) 1) Nx105(1:1) Nx106(1:1) 1) Nx110(1:1) Nx310(3:1) Nx315(3:1) Nx320(3:1) Nx330(3:1) Nx340(3:1) Nx350(3:1)
- Capacity: 3kVA/2.4kW, 5kVA/4kW, 6kVA/4.8kW, 10 kVA/8 kW ,10 kVA/8 kW, 15 kVA/12 kW, 20 kVA/16 kW 30 kVA/24 kW, 40 kVA/32kW ,50 kVA/40kW
- INPUT:
- Input wiring: Three-wire (L+N+E) Three-phase five-wire (3Phi + N + PE)
- Rated voltage: 220/230/240 Vac 380/400/415 Vac
- Voltage range: 145~285 Vac 285475 Vac
- Rated frequency: 50/60 Hz
- Frequency range: 40~70 Hz
- Bypass voltage range: ± 25% (settable)
- OUTPUT:
- Output wiring: Single-phase three-wire (1Phi + N + PE)
- Rated voltage: 220/230/240 Vac
- Output voltage regulation: ± 1%
- Rated frequency: 50/60 Hz (settable)
- Output frequency regulation: 50/60 Hz ± 0.1 Hz in battery mode
- Power factor: 0.8
- Voltage distortion (THDv): < 2% (linear load); ? 5% (non-linear load)
- Crest factor: 3:1
- Overload: 105%~125% for 10 min, 125%~150% for 1 min, 150% ~ 200% for 200 ms, > 200% for 100 ms
- BATTERIES:
- DC voltage: 192 Vdc
- Number of batteries: 12 V x 16 pcs
- Charging voltage: 216 Vdc
- EOD: 168 Vdc
- Charging current: Default 8 A (2A/4A/6A/8A/10A/12 A selectable)
- SYSTEM:
- Protections: Short-circuit, overload, overvoltage, undervoltage, low battery, overtemperature
- Communications: RS232/USB (standard); RS485/SNMP/dry contacts (optional)
- OTHERS:
- Operating temperature: 0~40?
- Storage temperature: - 25?~55? (without batteries)
- Relative humidity: 0~95% (non-condensing)
- Altitude: < 1000 m (derating 1% for each additional 100 m)
- IP rating: IP 20
- Noise level at 1 m: < 60 dB
- Dimensions (W x D x H) (mm) X X: 310 x 600 x 880 400 x 815 x 1100
- Packaged dimensions (WxDxH) (mm): 430 x 710 x 1080 525 x 925 × 1305
- Net weight (kg): 140 210 240 280
- Gross weight (kg): 153 225 255 295